LOAD CALCULATION
This is a
simplified method for doing a very rough calculation. Remember, electricians
and designers use rules that are much more complicated, so don't get ahead of
yourself.
Let's look
at a simple formula. HOUSE LOAD = BASIC LOAD + LARGE APPLIANCES + SPECIAL LOADS
BASIC LOAD include lighting, outlets, and smaller appliances including oil or
gas furnaces, central vacuums, pool pumps, waste disposals, etc., but NOT
baseboard heaters based on house size (square feet).
LARGE
APPLIANCES include electric stove, electric dryer and electric water heater.
SPECIAL LOADS include fixed electric heaters (most commonly baseboard heaters),
central air conditioners, etc.
Follow these
five steps: BASIC LOAD Estimate or measure house square footage. Include 75% of
any basement floor area. Don't use measurements based on the outside wall
surfaces.
Calculate
interior space. For the first 1,000 square feet, allow 5,000W. For each of the
next 1,000 square feet, or part thereof, add 1,000W. This gives a BASIC LOAD,
in watts.
LARGE
APPLIANCES a typical house has an electric stove and an electric water heater.
Note: Include these in the calculation even if the house presently has a gas
stove, for example, if you plan on changing appliances. Allow 6,000W for the
stove. Allow 750W for the electric water
heater. Allow 1,500W for any additional stoves. The total of these gives you
the LARGE APPLIANCES LOAD, in watts. Add the BASIC and LARGE APPLIANCES LOAD,
and divide by 240V to get a subtotal, in amps. Subtotal = (BASIC + LARGE
APPLIANCES)?
SPECIAL
LOADS find out any special loads the house may have. The load in amps is read
off the data plate on each appliance. Common special loads are (a). Electric
furnace (b). Electric baseboard or wall mounted heaters add up the wattage on
each data plate; divide the total by 240V to get amps (c). Central air
conditioner use the FLA (full load amps) HOUSE LOAD The house load is the sum
of the Subtotal and the Special Loads. Let's run through an example with a
2-story, 1,500 square foot home with 100-amp service. BASIC LOAD Each story is
750 square feet (1,500). Seventy-five percent of the basement area is: 75% x
750 = 562 sq. ft. Total area for calculations = 1500 + 562 = 2062 sq. ft. Use
5,000W for first 1,000 sq. ft.: 5,000W Use 1,000W for next 1,000 sq. ft.:
1,000W Use 1,000W for the last 62 ft.: 1,000W BASIC LOAD: 7,000W LARGE
APPLIANCES Electric Stove: 6,000W Dryer: 1,000W LARGE APPLIANCE LOAD: 7,000W
Subtotal: (7,000W + 7,000W) 240V = 58.3 Amps SPECIAL LOADS 2-ton air
conditioner with full load amperage rating (FLA) = 12 Amps 2 x 1,000W baseboard
heaters = 2,000W/240V = 8.3 Amps HOUSE
LOAD TOTAL (Subtotal plus special loads) 58.3A + 12A + 8.3A = 78.6 Amps This
house doesn't look like it has quite enough electricity. It's close, though, so
we recommend that the homeowner try it before committing to a service upgrade.
Remember that the baseboard heaters won't be on when the A/C is. But this
service cannot support any additional loads.